CÔNG TY TNHH CÔNG NGHỆ VNPOWER

Đc: 258/7 Vườn Lài, P.PTH, Q.Tân Phú, Tp.HCM
Tel: (+84 28) 66797915 - Fax: (+84 28) 39722274
Email: [email protected]
Website: www.vnpower.com.vn

THE UPS AND THE TRANSFORMER

We often hear of UPS transformers in reference to static UPS system technology (trafo or trafoless), isolation transformers and transformers for different neutral systems. Frequently however, the purpose of the transformer is not clear and  becomes confused, increasing the risk of incorrect technical choices. Here below you will find a short (but not exhaustive) illustration of the main differences and reasons for choosing one solution over another.

UPS technologies with transformer

A common opinion is that the Static UPS system with transformer guarantees galvanic isolation. This is only partly true. In fact, as you can see in Figure 1, isolation is assured exclusively for the inverter line.

Figure 1 – Example of UPS technology with Transforme

 

If the bypass line is not isolated, there is no guarantee of any input/output isolation on it. If galvanic separation is required, an additional transformer must be installed on the auxiliary input.

In fact, the transformer is used in the UPS to reconstruct the shape of the sine wave by adapting it to the output voltage value. These UPS can be used with their factory settings in the event of differences in the rectifier supply and the auxiliary supply as well as their neutrals.

When the trafoless UPS requires a transformer

Generally speaking, a UPS does not need a transformer. A UPS without a transformer normally requires a neutral to work. This engineering choice is linked to various factors, including improved yield, minimum floor space and reduced costs.

Figure 2 – Example of UPS technology without transformer

There are however some cases in which a transformer is required for static trafoless UPS:

  • when the neutral is not available to create it;
  • when there are two separate supplies, in order to avoid the grouping of different neutrals (see Figure 2);
  • when galvanic isolation is required and/or the neutral systems need altering

Conclusion

There is no general rule for choosing a UPS with or without a transformer, as the choice is linked to technical and economic considerations concerning the electrical system, as well as purchase and running costs.

The best thing to do is to contact the UPS supplier directly and provide the system features (e.g. presence or not of the neutral, need for isolation or presence of separate distribution networks for the main and auxiliary inputs). The supplier will be able to study the system constraints and propose the best solution.


Tech Info – May  2010

THE UPS AND THE TRANSFORMER

by

MATTEO GRANZIERO

Technical Communication Specialist

SOCOMEC UPS